Lube oil air-cooled heat exchangers oil type АВО-М are designed for cooling and condensation of gaseous, vapor and liquid products in the technological processes of oil refining, petrochemical, gas and related industries. The field of application is the cooling of low-pressure oil at compressor stations of main gas pipelines. Heat exchangers are designed to replace ones of Hungarian origin with horizontal arrangement of heat-exchangingbays installed on supporting metal structures.

Lube oil air-cooled heat exchangers oil type АВО-М are designed for cooling and condensation of gaseous, vapor and liquid products in the technological processes of oil refining, petrochemical, gas and related industries. The field of application is the cooling of low-pressure oil at compressor stations of main gas pipelines. Heat exchangers are designed to replace ones of Hungarian origin with horizontal arrangement of heat-exchangingbays installed on supporting metal structures.

Specification

Parameters

Values

Heat exchanging area:

1080 m2

Tube finned surface factor (nominal):

9,8

Finned tube length:

4,94 m

No of tube rows:

6

No of tube passes:

6

No of tubes per bay:

321

Tube joint type:

extruded

Agitator type:

tape insert

Inlet and outlet nominal diameter:

100 mm

Operating temperature of cooled medium:

not more than 100 °С

Excess operating pressure/design pressure:

0,7 МPа/0,7 МPа (7 kg/сm2/7kg/сm2)

Design temperature (for strength):

150 °С

Minimal temperature of details wall working under excess pressure:

- 40 °С

Design parameters of bay operation of lube oil ACHE:

Lube oil flow rate:

37,8 m3/h

Inlet/outlet temperature of lube oil:

65 °С /51 °С

Design air temperature:

35 °С

Fan impeller type:

axial

Fan impeller diameter:

1,25 m

Fan impeller rotating speed:

960 rev/min

No of fans:

2

Capacity of one E-motor (generating):

5,5 kW

Explosion protection:

1ЕхdllВ3Т4

Supply voltage:

380 V

Main material:

tubes – aluminium АД1; the rest – CS.

Remark: the maximum deviation of the actual heat exchanging area of the bay from the minimum - minus 5%, the deviation towards the increase is not regulated. The fans are driven by electric motors, on the shaft of which the fan impellers are arranged.